| 1 Assembly 15 KV MEDIUM VOLTAGE SWITCHGEAR(4
Feeders) |
| Type |
|
Free-standing, Indoor |
| Voltage |
|
13.2kv, 3 phase, 60Hz |
| Control Volt |
|
240 Vac |
| Enclosure |
|
Medium Voltage switchgear for indoor use, type one
high, made from B.I. steel sheet Gauge #12 for the structure and Ga#14 for the
covers and panels. All doors shall be gasketed neoprene type. The Versa modular
MV switchgear enclosure design shall be
bolted together to form a rigid and stable structure.
The enclosure shall be in accordance with IEC649/IEC298 with equivalent ANSI
C37.20.2, indoor application. |
| Paint |
|
The enclosure shall be clean with the advance metal
Treatment process (degreasing, derusting, metal, conditioning and zinc phosphating).
Powder coated, Oven baked for indoor use. |
| Dimension |
|
2100mm H x 1700mm D x 800mm W approx. |
| Quantity |
|
3 Vertical Section |
| |
|
|
| The enclosure shall house the following components
as follows: |
| Vertical Section # 1: (Station Service Transformer) |
| 1 unit |
|
Station Service Transformer, Oil Immersed rated 10kVA, single
phase, 60
Hz., 7620/120-240Vac |
| 1 unit |
|
Transformer Differential Relay (87T) |
| 3 units |
|
Potential transformer 13.2kV/240-120Vac, 70:1, 60Hz, 1-phase
with
primary CLF fuses, ANSI metering accuracy. |
| 9 pcs |
|
Current Transformer rated 600:5A, Torroidal type, metering
and elaying
accuracy. |
| 1 set |
|
Overcurrent & Ground Fault, Instant/Inverse Time Delay
Relay (50/51/50N/51N) (protection for 69kV SF6 CB) |
| 1 pc |
|
Digital Multi-meter capable of indicating voltage, power
(kw, kvar,
kva), energy, current, power factor, frequency, harmonics etc. |
| 1 pc |
|
Thermostat control switch, 60 - 250 degrees F, 240Vac |
| 1 pc |
|
Space heater, 300W, 240Vac |
| 1 set |
|
Lighting fixtures, 20W, 220Vac including limit switch |
| 1 set |
|
AC/DC Panel with 1 main and 6 branches. |
| 1 set |
|
Battery Bank, 125Vdc, 60AH, station type, 2V/cell |
| |
|
|
| Vertical Section # 2 & 3 (Outgoing
Feeder) |
| 4 units |
|
SF6 Circuit Breaker, rated 630A, 15kv, short circuit 25ka
interrupting
capacity, for indoor installation, fixed type, electrically and manually operated
complete with motor spring charge and shunt trip, control voltage 240Vac, 2NO-2NC
auxiliary contacts with standard accessories i.e. Manual Spring Charging Lever. |
| 4 sets |
|
Overcurrent & Ground Fault, Instant/Inverse Time Delay
Relay (50/51/50N/51N) |
| 4 pcs |
|
Digital Multi-meter capable of indicating voltage, power
(kw, kvar,
kva), energy, current, power factor, frequency, harmonics etc.
24 pcs Current Transformer rated 300:5A, Torroidal type, metering and relaying
accuracy. |
| 4 pcs |
|
Circuit Breaker Control Switch |
| 12 pcs |
|
Lightning Arrester, Distribution type, 10kv. |
| 4 pcs |
|
Thermostat control switch, 60 - 250 degrees F, 240Vac |
| 4 pcs |
|
Space heater, 300W, 240Vac |
| 4 sets |
|
Lighting fixtures, 20W, 240Vac including limit switch |
| 4 sets |
|
CTT / PTT, 10 pts. |